| Overpressure Protection Device : |
For the purposes of this standard, a device which under abnormal conditions will act to reduce, restrict or shut off the supply of gas flowing into a system to prevent gas pressure in that system from exceeding 2 psi (13.8 kPa). |
| Line Pressure Regulator : |
A gas pressure regulator intended for installation in a building gas distribution system between the building service regulator or LP-gas 2 psi service regulator and gas utilization equipment.
For purposes of this standard, a line pressure regulator is rated for an inlet gas pressure of either 2, 5, or 10 psi (13.8, 34.5, or 68.9 kPa) and is designated as either Class l or Class ll as follows:
• Class l - Maximum outlet pressure of 1/2 psi (3.5 kPa)
•
Class ll - Maximum outlet pressure of 2 psi (13.8 kPa) |