Attention: |
To comply with the ANSI Z21.80 standard for Line Pressure Regulators, installations exceeding 2 psi nominal require a tested and approved over pressure protection device (OPD) for use with the regulator. |
Maximum Inlet Pressure: 5 psi (345 mbar), CSA Certified
Emergency Exposure Limits: 65 psi (4.5 bar), (inlet side only)
Outlet Pressure Range: 7-11" w.c., Certified Spring
Maximum Individual Load / Capacity (regulator w/OPD) :
325-3L47 (3/8", 1/2") ......................................................................................... 125,000 Btu/hr
325-3L48 (1/2") .................................................................................................. 200,000 Btu/hr
325-5AL48 (1/2") ................................................................................................ 235,000 Btu/hr
325-5AL48 (3/4") ................................................................................................ 320,000 Btu/hr
325-5AL600 (3/4") .............................................................................................. 425,000 Btu/hr
325-5AL600 (1") ................................................................................................. 465,000 Btu/hr
325-7L210D (1 1/4", 1 1/2") .............................................................................. 900,000 Btu/hr
Venting:
OPD 47 (integral vent limiting orifice w/dust cap)
OPD 48 (optional 12A09 vent limiter), 1/8" NPT
OPD 600 (optional 12A09 vent limiter), 1/8" NPT
OPD 210 (must be vented outdoors), 1/2" NPT
325-7L (must be vented outdoors)
Gases: Suitable for natural, manufactured, mixed gases, liquefied petroleum gases and LP gas-air mixtures.
Ambient Temperature Limits: -40ºF to 205ºF (-40ºC to 96ºC)
Certification: |
Maxitrol's 325 L Series with overpressure protection device (OPD) are CSA certified (Z21.80) for 5 psi maximum inlet pressure, and outlet pressure range of 7 to 11 inches w.c.
|
325-3L47
325-3L48
325-5AL48
325-5AL600
325-7L210D
NOTE: Installations MUST be performed in accordance with local codes or, in absence of local codes, in accordance with the NFPA 54 / ANSI Z223.1.
|
|
 |
The 325 Series with OPD is suitable for limited horizontal mounting (less than or equal to 90º from upright). But when using the vent limiting device, the regulator must be mounted in a horizontal upright position. Install the regulator properly with gas flowing as indicated by the arrow on the casting (also see the Safety Warning Instructions bulletin). |
NOTE: |
Vent limiters can only be installed in regulators for which they are certified. Vent limiters must only be installed directly into the vent connection of the regulator without intermediate pipe or fittings.
|
|