2PSI - SPECIFICATIONS FOR 2PSI PIPING SYSTEMS

Maximum Inlet Pressure: 2 psi (140 mbar), CSA Certified

Emergency Exposure Limits: 65 psi (4.5 bar), (inlet side only)

Outlet Pressure Range: 7-11" w.c., Certified Spring

Maximum Individual Load - Largest single appliance served by the regulator:
325-3L .......................................................................................... 140,000 Btu/hr
325-5AL ........................................................................................ 300,000 Btu/hr
325-7L .......................................................................................... 900,000 Btu/hr

Capacity - Total load of all appliances combined:
325-3L (3/8", 1/2") ................................. 250,000 Btu/hr
325-5AL (1/2") ....................................... 425,000 Btu/hr
325-5AL (3/4", 1") .................................. 550,000 Btu/hr
325-7L (1 1/4", 1 1/2") .......................... 1,000,000 Btu/hr

Venting:
325-3L (optional 12A09 vent limiter), 1/8" NPT
325-5AL (optional 12A39 vent limiter), 3/8" NPT
325-7L (must be vented outdoors), 1/2" NPT

Gases: Suitable for natural, manufactured, mixed gases, liquefied petroleum gases and LP gas-air mixtures.

Ambient Temperature Limits: -40ºF to 205ºF (-40ºC to 96ºC)

Certification:

Maxitrol's 325 L Series regulators are CSA certified (Z21.80) for 2 psi inlet pressure, outlet pressure range of 7 to 11 inches w.c.


325-3L
325-5AL
325-7L

NOTE:
Installations MUST be performed in accordance with local codes or, in absence of local codes, in accordance with the NFPA 54 / ANSI Z223.1.
The 325 Series is suitable for multi-positional mounting. But when using the vent limiting device, the regulator (325-3L, 325-5AL) must be mounted in a horizontal upright position. Install the regulator properly with gas flowing as indicated by the arrow on the casting (also see the Safety Warning Instructions bulletin).
NOTE:

Vent limiters can only be installed in regulators for which they are certified. Vent limiters must only be installed directly into the vent connection of the regulator without intermediate pipe or fittings.

 
 
© 2007 Maxitrol Company. All rights reserved